Implement Industry Ideas
  • Isolation transformer / three-winding / encapsulated / three-phase

DS0107 series

Article: 00038485

Isolation transformer / three-winding / encapsulated / three-phase

The transformers in the DS0107 series are noted for their reinforced insulation. They cater to the standards mandated in IEC 61558-2-15 DIN EN 61558-2-15 (VDE 0570-2-15) and IEC 61558-1, DIN EN 61558-1 (VDE 0570-1). Additional security for IT systems in medical locations is ensured with IEC 60364-7-710 / DIN VDE 0100-710 (VDE 0100-710). Galvanical isolation of windings is possible. An electrostatic screen, installed between primary and secondary winding reduces electrical interferences; the lead is connected to an insulated terminal to enable equipotential bonding. DIN VDE 0100-710 (VDE 0100-710): 2002-11, para 710.512.1.6.2) specify isolated installation, this is followed by the transformers whose fixing angles are isolated from the transformer core. Both vertical and horizontal installation possible.

Specifications

  • Configuration: three-winding, encapsulated
  • Electrical characteristics: three-phase
  • Applications: for medical applications
  • Other characteristics: isolation
  • Current: Min.: 3 A
  • Electric power: Min.: 2 kVA (2.68 hp)

Other items

In this category | In this category, (BENDER)

Leave request for price calculation right now, we will send you best prices.