  • Fault locator for overhead lines

MS1S26

Article: 00048952

Fault locator for overhead lines

Arc fault monitor with up to 8 arc fault sensors connections in 4 independent tripping zones. A trip signal can be achieved within 10 ms with a three phase overcurrent check facility

Arc fault protection is a relatively new technique employed for the fast clearance of arcing faults on BUS bars & within metal clad switchgear & associated cable boxes. The arc is detected using an optical sensor & the signal input to a protection device which also monitors the load current on the system. A trip signal can be achieved in less than 10ms using arc detection only or within 15ms when using the integrated instantaneous overcurrent check. This is considerably faster than a traditional IDMT overcurrent relay & provides additional protection from the onset of arcing faults with relatively low fault currents.

BUS PROTECTION
The 1S26 Arc Fault relay is designed for application on new or existing medium voltage BUS systems with up to two incoming lines. For new installation the high speed arc protection technique offers cost advantages over traditional high impedance differential schemes. For existing installations which may not have any BUS protection or using simple earth leakage protection it is relatively simple & cost effective to retrofit an arc protection scheme as dedicated protection CT?s are not required.

Specifications