24 VAC | ARP23S

Article: 00086995

Solid-state relay / control / alternating / DIN rail

Hie ARP Series is used in systems where equal
run time for two motors is desirable. Hie selector
switch allows selection of alternation of either load
for continuous operation. LED's indicate the status
of the output relay. This versatile series may be
front panel mounted (BZ1 accessory required) or
35 mm DIN rail mounted with an accessory socket.
For more information see:
Appendix B, page 167, Figure 31 for dimensional drawing.
Appendix C, 170, Figure 29 for connection diagram.
Operation
Alternating: When the rotary switch is in the "alternate" position, alternating operation of Load A and Load B
occurs upon the opening of the control switch SI. To terminate alternating operation and cause only the selected
load to operate, rotate the switch to position "A" to lock Load A or position "B" to lock Load B. The LEDs indicate
the status of the internal relay and which load is selected to operate.
Note: Input voltage must be applied at all times for proper alternation. The use of a solid-state control switch
for SI may not initiate alternation correctly. SI voltage must be from the same supply as the unif s input
voltage (see connection diagrams). Loss of input voltage resets the unit; Load A becomes the lead load for
the next operation.
Duplexing (Cross Wired): Duplexing models operate the same as alternating relays and when both the Control
(SI) and Lag Load (S2) Switches are closed, Load A and Load B energize simultaneously.
The DPDT 8-pin, cross-wired option, allows extra system load capacity through simultaneous operation of both
motors when needed. Relay contacts are not isolated.

Specifications

  • Type: solid-state
  • Function: control, alternating
  • Form: DIN rail
  • Applications: general purpose