8 A, 85 - 265 V, max. 4.5 VA | CO13XXL

Article: 00086575

Electromechanical relay / emergency stop / DIN rail

Performance level with AWAX controller: PL = d

Safety category: 3 (two-channel)

Safety Integrity Level: SIL 2

Time before dangerous failure: MTTFd = 240 years

Cycle before dangerous failure: B10d=100,000 at 5A

Risk duration: 20 ms max.

Cable severing protection: yes (opening of safety lines)

Safety contacts/diagnostics: 2x NO 8A/250V redundant / 1x NF 8A/250V parallel redundant + 1x NO static 400 mA

Indicators: 3 LEDs for diagnostics

Reset: configurable by dip-switch (SR=Automatic, N=manual)

Mounting: symmetrical DIN 35mm rail on DIN 50022

Mounting: IP 54 electrical box

Electrical connection: Maximum 14 AWG (2.08 mm²) / 250V minimum

Temperature: -20°C to +60°C

Specifications

  • Type: electromechanical
  • Function: emergency stop
  • Form: DIN rail

Other items

In this category | In this category, (Comitronic Bti)

Leave request for price calculation right now, we will send you best prices.